The image contains a red and black logo with the text 'mHeat' in a stylized font.

The mHEAT KAPI is a Mayekawa plug-and-play standard solution with a strong focus on innovative design, energy efficiency and durability.

The mHEAT KAPI is a standard water-to-water low charge ammonia heat pump designed to deliver best-in-class efficiency, small footprint, and the best sustainable solution. The MYCOM HSIII series of compressors ensures maximum efficiency even in part load conditions. The mHEAT  series has been designed for easy and simple installation and a long lifespan. The mHEAT KAPI is designed to meet the needs of industrial markets such as district heating, waste energy recovery, breweries, industrial processes, data centers, building facilities etc.

It is designed with ammonia, a natural refrigerant that gives the highest energy efficiency and the best sustainable solution.

The mHEAT KAPI can provide up to a supply temperature of 90°C with its 60 bar design. It runs with the proven MYCOM HSIII compressor which combines efficiency with reliable robust performance and maintenance with high lift capabilities.

The integrated system cooling of the mHEAT KAPI will ensure minimal ambient heat rejection helping reduce machine room energy consumption. The water-cooled architecture of the mHEAT KAPI also enables a very compact footprint.

All heat pumps come with an EOLT Report (End of line test) that is performed at our factory. The EOLT includes a full load thermal performance test, thermal imaging of key points, and vibration measurements.

Key features & Benefits

Source, low temperature Supply, high temperature
Source, low temperature
Process
waste heat
Combined
process cooling
Groundwater/
surface water
Waste
water
Supply, high temperature
Hot water/
washdown
Space
heating
Process
heating
District
heating

Technical Info

Heat Pump Performance Table
Hot side (in/out) 40/60 °C 50/70 °C 60/80 °C 70/90 °C
Cold side (in/out) 25/20 °C 30/25 °C 35/30 °C 40/35 °C
General
Refrigerant/charge R717 / 125 kg
Capacity range 20-100 %
Heating capacity 1145 kW 1279 kW 1419 kW 1513 kW
Cooling capacity 964 kW 1055 kW 1146 kW 1194 kW
Total absorbed power 198 kW 243 kW 295 kW 344 kW
COP 5.8 (-) 5.3 (-) 4.8 (-) 4.4 (-)
EER 4.9 (-) 4.4 (-) 3.9 (-) 3.5 (-)
Heat sink (Condenser) / Heat source (Evaporator)
Secondary media Water
Hot side flow rate 50 m3/h 56 m3/h 62 m3/h 67 m3/h
Cold side flow rate 166 m3/h 182 m3/h 198 m3/h 207 m3/h

*All information is subject to change without notice.

Electrical
ModelKAPI 600R
System earthing TN-S
Input voltage 3X400VAC+PE, 50 Hz
Rated package current 700 A
IK Max. 20 kA
Maximum fuse 800 A
Communication ModBus TCP/IP, OUC
Power supply Top feed
Environmental
ModelKAPI 600R
Sound pressure (1m) 85 ± 2 dB(A)
Sound pressure (10m) 65 ± 2 dB(A)
Surroundings (operation) 40 °C / 10 °C, 90% rh, 1000m
Vibration-damping feet Standard
GWP 0
Location Machinery room / Outdoor (Optional)
DESIGN PARAMETERS
Design pressure - discharge side 60 bar
Design pressure - suction side 25 bar
Design temperature -20 / 170°C
Connections - Secondary media DN 100
Design pressure - Secondary media 16 bar
DIMENSIONS AND WEIGHT
Length (L) 5200 mm
Width (W) 1500 mm
Height (H) 2400 mm
Dry weight 12000 kg
Standard colour RAL 7035